WATER FIRED SINGLE-EFFECT
ABSORPTION CHILLER AND CHILLER-HEATER
This product is a water fired absorption unit which provides chilled water for cooling or hot
water for heating in central plant type air conditioning systems. Units with nominal refrigeration
capacities of 10, 20, and 30 tons are complete with operating and safety controls. The
absorption chiller or chiller-heater is energized by a heat medium (hot water) at 158
o
F to 203
o
F
from a process, cogeneration, solar or other waste heat source.
When this equipment is applied correctly, installed in accordance with Yazaki
INSTALLATION INSTRUCTIONS and properly maintained, it will provide many years of trouble
free operation.
CONTENTS
GENERAL Page
ABSORPTION PRINCIPLE 2
COOLING OPERATION 2
HEATING OPERATION 3
CONTROLS
GENERAL INFORMATION 5
CONTROL ADJUSTMENTS 8
CONTROL SEQUENCE 8
OPERATION
COOLING 10
HEATING 10
REMOTE CONTROL 10
WINTER SHUTDOWN 10
Page
SAFETY CONTROLS 10
PRECAUTIONS 10
MAINTENANCE
GENERAL INFORMATION 11
ROUTINE MAINTENANCE 11
WINTERIZING 11
WATER QUALITY 12
TROUBLESHOOTING GUIDE 12
ERROR CODES 13
WARRANTY
YAZAKI LIMITED EXPRESS
WARRANTY 15
OPERATING INSTRUCTIONS
WFC-SC10, 20, 30
WFC-SH10, 20, 30
Page view 0
1 2 3 4 5 6 ... 15 16

Summary of Contents

Page 1 - WATER FIRED SINGLE-EFFECT

WATER FIRED SINGLE-EFFECTABSORPTION CHILLER AND CHILLER-HEATERThis product is a water fired absorption unit which provides chilled water for cooling o

Page 2 - COOLING OPERATION

10OPERATIONCOOLING1. Select STOP on the REMOTE-STOP-RUNswitch to stop heating operation. (If currentlyoperating in the heating mode.)2. Push COOLING

Page 3 - HEATING OPERATION

11MAINTENANCEGENERAL INFORMATIONALL MAINTENANCE SHOULD BE PERFORMED BY SKILLED, EXPERIENCEDPERSONNEL. Your Authorized Yazaki ServiceProvider can help

Page 4

12WATER QUALITYIt is the Owner/End User’s responsibility to have the cooling water analyzed and chemicallytreated (as often as necessary) so that it c

Page 5 - CONTROLS

13SYMPTOM: Poor cooling capacityPOSSIBLE CAUSE REMEDYPoor vacuumEvacuate noncondensible gases from the vacuum section throughservice valves A and B. L

Page 6

14ERRORCODEDESCRIPTION REMARKSE29-E32 NACTI (cooling water temperature sensor)Shutdown when open circuit (<14.4oF)E33wire open circuitdetected for

Page 7 - WFC-TRUL1

15WARRANTYYAZAKI LIMITED EXPRESS WARRANTY1. Scope of Coverage. The Limited Express Warranty of Yazaki Energy Systems, Inc ( Company ) applies to the

Page 8 - CONTROL SEQUENCE

16AUTHORIZED YAZAKI SERVICE PROVIDERFor information concerning service, operationor technical assistance, please contact yourAuthorized Yazaki Service

Page 9

GENERAL2These instructions are intended to acquaintthe Owner/End User with the operation and general maintenance requirements of YazakiWater Fired Sin

Page 10 - OPERATION

3HEATING OPERATIONGeneratorWhen the heat medium inlet temperatureexceeds 154.4oF (203oF max.) the solution pump forces dilute lithium bromide solution

Page 11 - MAINTENANCE

4Fig.2 SINGLE-EFFECT ABSORPTION CYCLE (HEATING)EvaporatorHot refrigerant vapor condenses on the surface of the evaporator coil and heat, equivalent to

Page 12 - TROUBLESHOOTING GUIDE

5CONTROLSGENERAL INFORMATIONA control panel, shown in Fig. 3, is builtinto each absorption chiller or chiller-heater and is located on the control box

Page 13 - ERROR CODES

6Chiller or Chiller-HeaterFig. 4 LOCATION OF CONTROLSFuse PanelREPLACEMENT FUSESSYMBOL RATING TYPEFT1, FT2 5AFuji ModelF11, F12 2A FGAO-2 ratedF4 2A25

Page 14 - NOTE: NA (Not Applicable)

SOLUTION PUMP THERMALOVERLOAD SETTINGS (A)MODEL SYMBOL 208VWFC-SC10THRP 0.4WFC-SH10WFC-SC20THRP 0.7WFC-SH20WFC-SC30THRP 2.0WFC-SH30The 208V, 60Hz, 3 p

Page 15 - WARRANTY

8CONTROL ADJUSTMENTSThe leaving chilled water and hot water temperature controls are set at the factory to theStandard Specifications shown in Fig. 5.

Page 16 - OP-WFCS-0507

Normal StopBy Temp ControlStartHM PumpOn (Note)C/H WaterPump OnC/HWTR/PumpOPGNoYesStopC/HWaterTempOperationHeatingCLG/HTGCoolingCW Pump OnNoCWPumpOPGY